{"id":7915,"date":"2020-01-10T10:00:00","date_gmt":"2020-01-10T09:00:00","guid":{"rendered":"https:\/\/www.idro-elettrica.it\/esperto-risponde\/reuse-of-fire-protection-water-reservoirs-7-checks\/"},"modified":"2026-07-01T09:46:15","modified_gmt":"2026-07-01T07:46:15","slug":"reuse-of-fire-protection-water-reservoirs-7-checks","status":"publish","type":"esperto-risponde","link":"https:\/\/www.idro-elettrica.it\/en\/esperto-risponde\/reuse-of-fire-protection-water-reservoirs-7-checks\/","title":{"rendered":"Reuse of Fire Protection Water Reservoirs: 7 Checks"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\"><em>Reuse of Fire Protection Water Storage Tanks<\/em>: When designing a pumping station for a textile plant, it is common to be asked to reuse existing tanks. The answer is \u201cyes, but\u201d\u2014and it depends primarily on the configuration and inlet layout.* <\/p>\n\n<div class=\"wp-block-rank-math-toc-block\" id=\"rank-math-toc\"><h2>Table of Contents<\/h2><nav><ul><li class=\"\"><a href=\"#il-caso-in-sintesi\">The Case in Brief<\/a><\/li><li class=\"\"><a href=\"#riutilizzo-dei-serbatoi-cosa-e-ammesso-in-linea-generale\">Reuse of Tanks: What Is Generally Permitted<\/a><\/li><li class=\"\"><a href=\"#riutilizzo-serbatoi-riserva-idrica-antincendio-sopra-o-sotto-battente\">Reuse of Fire Protection Water Reserve Tanks: Above or Below the Water Level?<\/a><\/li><li class=\"\"><a href=\"#il-collettore-di-aspirazione-quando-e-ammesso-e-quando-e-vietato\">The Inlet Manifold: When It Is Permitted and When It Is Prohibited<\/a><\/li><li class=\"\"><a href=\"#due-serbatoi-non-comunicanti-affidabilita-e-continuita-della-riserva\">Two separate tanks: reliability and continuity of the reserve<\/a><\/li><li class=\"\"><a href=\"#attenzione-al-livello-minimo-la-portata-di-progetto-deve-restare-garantita\">Watch the minimum level: the design flow rate must be maintained<\/a><\/li><li class=\"\"><a href=\"#cosa-serve-per-una-risposta-davvero-univoca-e-senza-rischi\">What It Takes for a Truly Unambiguous (and Risk-Free) Answer<\/a><\/li><li class=\"\"><a href=\"#conclusione\">Conclusion<\/a><\/li><\/ul><\/nav><\/div>\n\n<h2 id=\"il-caso-in-sintesi\" class=\"wp-block-heading\">The Case in Brief<\/h2>\n\n<p class=\"wp-block-paragraph\">You are designing a fire pump station and want to reuse <strong>two vertical iron tanks<\/strong> already on site, <strong>each measuring 20 m\u00b2<\/strong> and <strong>3 meters high<\/strong>, <strong>which are not connected<\/strong> to each other.<\/p>\n\n<p class=\"wp-block-paragraph\">The two key questions are:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>whether these tanks can be used as <strong>a water reserve<\/strong>;<\/li>\n\n\n\n<li>whether the installation should be considered <strong>above<\/strong> or <strong>below the door frame<\/strong>.<\/li>\n<\/ul>\n\n<h2 id=\"riutilizzo-dei-serbatoi-cosa-e-ammesso-in-linea-generale\" class=\"wp-block-heading\">Reuse of Tanks: What Is Generally Permitted<\/h2>\n\n<p class=\"wp-block-paragraph\">The tanks <strong>can be reused<\/strong> as a water reserve. However, to ensure that the solution is technically compatible with the system, a connection to the pumps must be provided via an <strong>inlet manifold<\/strong>, which must be <strong>properly sized<\/strong>. <\/p>\n\n<p class=\"wp-block-paragraph\">This point is not merely a \u201csystem-related\u201d detail: it is one of the factors that determines the feasibility of the configuration and, above all, the ability of the water supply system to maintain the required performance.<\/p>\n\n<h2 id=\"riutilizzo-serbatoi-riserva-idrica-antincendio-sopra-o-sotto-battente\" class=\"wp-block-heading\">Reuse of Fire Protection Water Reserve Tanks: Above or Below the Water Level?<\/h2>\n\n<p class=\"wp-block-paragraph\">The classification of the installation as <strong>\u201cabove the door\u201d<\/strong> or <strong>\u201cbelow the door\u201d<\/strong> cannot be automatically determined solely on the basis that there are two tanks that are not connected.<\/p>\n\n<p class=\"wp-block-paragraph\">The <strong>definitions<\/strong> that describe the <strong>above- and below-flange<\/strong> configurations are specified in <strong>UNI EN 12845, section 10.6.2<\/strong>. In practice, to answer correctly, you need to check the actual layout of the tanks, inlets, and pumps. <\/p>\n\n<p class=\"wp-block-paragraph\">Based solely on the information provided in the question, <strong>it is not possible to give a definitive answer<\/strong>.<\/p>\n\n<h2 id=\"il-collettore-di-aspirazione-quando-e-ammesso-e-quando-e-vietato\" class=\"wp-block-heading\">The Inlet Manifold: When It&#8217;s Allowed and When It&#8217;s Prohibited<\/h2>\n\n<p class=\"wp-block-paragraph\">There is a very clear restriction here:<\/p>\n\n<ul class=\"wp-block-list\">\n<li>The <strong>inlet manifold leading to the pumps<\/strong> (if properly sized) is <strong>acceptable<\/strong> if the application is <strong>a suction-fed system<\/strong>.<\/li>\n\n\n\n<li>The <strong>inlet manifold is prohibited<\/strong> in <strong>over-the-door<\/strong> applications, in accordance with <strong>UNI EN 12845, 10.6.2<\/strong>.<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">This means that, even before \u201cadapting\u201d the solution to existing tanks, it is best to start by asking a guiding question: <em>Does the configuration I am designing fall under the \u201csub-batten\u201d category (where the collector is permitted) or the \u201cover-batten\u201d category (where it is prohibited)?<\/em><\/p>\n\n<h2 id=\"due-serbatoi-non-comunicanti-affidabilita-e-continuita-della-riserva\" class=\"wp-block-heading\">Two separate tanks: reliability and continuity of the reserve<\/h2>\n\n<p class=\"wp-block-paragraph\">When there is no <strong>single water supply<\/strong>, this setting must be handled with particular care. The reference cited is <strong>UNI\/TR 11438 (4.1.3)<\/strong>, which states that: <\/p>\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p class=\"wp-block-paragraph\">\u201cSituations other than those involving a single water supply must be engineered to guarantee the system\u2019s required performance in all cases and to ensure the continuity and reliability of the water supply throughout its expected service life, even in the event of a fire.\u201d<\/p>\n<\/blockquote>\n\n<p class=\"wp-block-paragraph\">In practical terms (without adding requirements that aren&#8217;t already there): with two separate tanks, you must <strong>design and verify<\/strong> the solution so that the water supply remains <strong>continuous and reliable<\/strong> for the expected service life, even under fire conditions.<\/p>\n\n<h2 id=\"attenzione-al-livello-minimo-la-portata-di-progetto-deve-restare-garantita\" class=\"wp-block-heading\">Watch the minimum level: the design flow rate must be maintained<\/h2>\n\n<p class=\"wp-block-paragraph\">One specific point to note is the following: care must be taken when <strong>calculating the manifold<\/strong>, because the <strong>design flow rate<\/strong> must be guaranteed <strong>even when the tanks are at their minimum level<\/strong>.<\/p>\n\n<p class=\"wp-block-paragraph\">This sentence alone makes it clear why the assessment cannot be limited to \u201ccan be reused \/ cannot be reused.\u201d Reusability is linked to: <\/p>\n\n<ul class=\"wp-block-list\">\n<li>inlet diagram;<\/li>\n\n\n\n<li>top\/bottom sash configuration;<\/li>\n\n\n\n<li>Performance testing when the water level in the tanks is at a minimum.<\/li>\n<\/ul>\n\n<h2 id=\"cosa-serve-per-una-risposta-davvero-univoca-e-senza-rischi\" class=\"wp-block-heading\">What It Takes for a Truly Unambiguous (and Risk-Free) Answer<\/h2>\n\n<p class=\"wp-block-paragraph\">The question is correct and very practical, but the information provided is not sufficient to definitively classify the system as top-hung or bottom-hung.<\/p>\n\n<p class=\"wp-block-paragraph\">To complete the verification correctly, the logical steps are:<\/p>\n\n<ol class=\"wp-block-list\">\n<li>classify the configuration according to the definitions in <strong>UNI EN 12845 (10.6.2)<\/strong>;<\/li>\n\n\n\n<li>Set up the layout, taking into account the constraint on <strong>the inlet manifold<\/strong> (allowed below the header, prohibited above the header);<\/li>\n\n\n\n<li>\u201cengineer\u201d the solution when there is more than one reserve, in accordance with <strong>UNI\/TR 11438 (4.1.3)<\/strong>;<\/li>\n\n\n\n<li>Verify that the <strong>design flow rate<\/strong> is maintained even when the reservoirs are at <strong>their minimum level<\/strong>.<\/li>\n<\/ol>\n\n<h2 id=\"conclusione\" class=\"wp-block-heading\">Conclusion<\/h2>\n\n<p class=\"wp-block-paragraph\">Yes, the two existing tanks can be reused as a water reserve, but the system must be configured correctly: the <strong>inlet manifold<\/strong> is a critical component (allowed in <strong>under-beam systems<\/strong>, prohibited in <strong>over-beam systems<\/strong>), and with two unconnected tanks, the design must ensure <strong>performance, continuity, and reliability<\/strong> down to the minimum level.<\/p>\n\n<p class=\"wp-block-paragraph\"><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Reuse of Fire Protection Water Storage Tanks: Existing tanks can be reused, but their configuration (top-fed\/bottom-fed) and the inlet manifold must be carefully evaluated. The definitions and requirements are specified in UNI EN 12845 (10.6.2) and UNI\/TR 11438 (4.1.3). <\/p>\n","protected":false},"featured_media":7916,"parent":0,"template":"","meta":{"_acf_changed":false,"_angie_page":false,"footnotes":"","_members_access_role":[],"_members_access_error":""},"tags":[],"class_list":["post-7915","esperto-risponde","type-esperto-risponde","status-publish","has-post-thumbnail","hentry"],"acf":[],"_links":{"self":[{"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/esperto-risponde\/7915","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/esperto-risponde"}],"about":[{"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/types\/esperto-risponde"}],"version-history":[{"count":0,"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/esperto-risponde\/7915\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/media\/7916"}],"wp:attachment":[{"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/media?parent=7915"}],"wp:term":[{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.idro-elettrica.it\/en\/wp-json\/wp\/v2\/tags?post=7915"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}