Outdoor water reserves

Outdoor water reserves - Idro-elettrica S.p.A.

Idroelettrica outdoor fire‑water reservoir: monobloc tanks fabricated from Fe360B / S235JR steel, pressure‑tested and fitted with anti‑corrosion protection and plant‑connection provisions for safe, controlled tank operation.

  • Tank capacity up to 160 m³ geometric
  • Tank capacity up to 140 m³ effective

Outdoor firefighting water reserve is the solution designed for storing service water for firefighting systems when an accessible, inspectable tank that is easily integrated with the pumping station is required. Idroelettrica S.p.A. manufactures monobloc tanks for outdoor installation, fabricated from Fe360B – S235JR steel (UNI EN 10025‑2) and supplied complete with handling equipment and plant connection fittings.
Fabrication is carried out under qualified procedures: welds are executed by personnel certified to UNI EN 287/1 using IT‑SG3 welding wire to achieve high‑strength joints (up to 600 N/mm²). Each tank is pressure-tested at 1.5 bar and protected with specialized anti-corrosion coatings: two-component epoxy on the exterior and gray two-component epoxy on the interior (for non-food applications).
From a functional standpoint, the tank can be configured to allow for continuous level monitoring and equipped with an anti-vortex plate, which helps limit the minimum head above the inlet and makes more complete use of the storage volume, as specified in UNI EN 12845. The result is a robust outdoor fire protection water reservoir, designed and verified through structural analysis, ready to be connected to pump-sets and replenishment systems.

Key Features

  • Monobloc tanks for outdoor firefighting water reserves
  • Material: Fe360B – S235JR (UNI EN 10025-2)
  • Equipped with lifting lugs for handling
  • Qualified UNI EN 287/1 welding with IT-SG3 wire (high strength up to 600 N/mm²)
  • 1.5 bar testing
  • Anti-corrosive external coating in two-component epoxy
  • Internal coating in grey two-component epoxy (non-potable use)
  • Arrangements for electrical and hydraulic connections

Advantages

  • Continuous tank level control (reference UNI EN 12845 H.2.4) for safer management
  • Arrangement for anti-vortex plate (reference UNI EN 12845/9.3.5) to limit the minimum head above the suction
  • Increased volume utilization: the anti-vortex plate allows for nearly full utilization of the tank capacity
  • Complete anti-corrosive protection for enhanced outdoor durability

Technical specifications

  • Static and dynamic design and testing using the limit state method, according to current standards
  • Calculation with Enexsys code and sizing of internal reinforcements
  • Reinforcements made with high-strength metal profiles (e.g., UPN 80, T60×60)
  • Construction features:
    • Walkable cover in checker plate aluminum
    • Overflow sleeve
    • Vent pipe of suitable diameter
    • Arrangement for system connections
    • Standard RAL 7035 finish with two-component anti-corrosive epoxy
    • Frost protection with thermostatic armored heating element (electrical connection by the customer)

Customizations

  • Arrangement and accessories for level measurement, replenishment, and signaling (based on project)
  • Design and supply of an anti-vortex plate based on the inlet configuration
  • Configuration of connections and accessories in accordance with the specification, and integration with the firefighting pump set.

Applications

Shopping Centers

Cinemas and theatres

Hotel complexes

Critical infrastructure

Industries

Healthcare facilities

Residential secto

School facilities

Oil & Gas